| SPÉCIFICATIONS GÉNÉRALES DU TRANSFORMATEUR  | 
| SPÉCIFICATIONS GÉNÉRALES  |   |   |   | 
| TYPE DE TRANSFORMATEUR  |   |   | Bain d'huile, hermétiquement scellé  | 
| INSTALLATION   |   |   | Extérieur  | 
| NORMES APPLICABLES  |   |   | CEI 60076-1  | 
| PUISSANCE NOMINALE  | (ONAN)  | KVA  | 250  | 
| HAUTE TENSION  |   | KV   | 15  | 
| MISES EN CORRESPONDANCE HAUTE TENSION (SANS CHARGE)  | %  | KV   | ±2 x 2,5 ou ±5 %  | 
| BASSE TENSION (SANS CHARGE)  |   | KV   | 0.4  | 
| NIVEAU D'ISOLATION HAUTE TENSION  | (UM/UAC/ULI)  | KV   | 24/50/125  | 
| NIVEAU D'ISOLATION BASSE TENSION  | (UM/UAC/ULI)  | KV   | 1 , 1 / 3 / --  | 
| FRÉQUENCE  |   | HZ  | 50  | 
| GROUPE DE VECTEURS  |   |   | Dyn11  | 
| NOMBRE DE PHASES  |   |   | 3  | 
| MAX. TEMPÉRATURE AMBIANTE  |   | C  | 40  | 
| MAX. MONTÉE DE TEMPÉRATURE (BOBINAGE / HUILE)  |   | C  | 65 / 60  | 
| MAX. ALTITUDE AU-DESSUS DE LA MER LEVELL  |   | m  | 1000  | 
| DURÉE DE COURT-CIRCUIT  |   | s  | 2  | 
| VALEURS GARANTIES  |   |   |   | 
| TENSION D'IMPÉDANCE (75 °C)  | tolérance de ±10%  | %  | 5.5  | 
| AUCUNE PERTE DE CHARGE  | tolérance de 1.5 à 5 %  | W  | 400  | 
| PERTES DE CHARGE (75C)  | tolérance de 3.5 à 8 %  | W  | 4210  | 
|   |   |   |   | 
| SPÉCIFICATIONS STRUCTURELLES  |   |   |   | 
| MATÉRIAUX CONDUCTEURS DE BOBINAGE HAUTE TENSION  |   |   | Cu  | 
| MATÉRIAUX DE CONDUCTEUR DE BOBINAGE BASSE TENSION  |   |   | Cu  | 
| TYPE D'HUILE  |   |   | Huile du transformateur minéral inhibée  | 
| MATÉRIAUX DU RÉSERVOIR  |   |   | Acier galvanisé  | 
| DIMENSIONS et POIDS  |   |   |   | 
| LONGUEUR /LARGEUR / HAUTEUR  |   | mm  | L / L / H   | 
| POIDS TOTAL  |   | kg  |   | 
| POIDS DE LA PIÈCE ACTIVE  |   | kg  |   | 
| POIDS DE L'HUILE  |   | kg  |   | 
|   |   |   |   | 
| BORNES DE CONNEXION  |   |   |   | 
| HAUTE TENSION   |   | Manchons ProClean 30 NF 250A x 3  |   | 
| BASSE TENSION  |   | Manchons ProClean 1 kV / A x 4  |   | 
|   |   |   |   | 
| ACCESSOIRES  |   |   |   | 
|  RELAIS DE PROTECTION HERMITICAL  |   |   |   | 
| DISPOSITIF DE DÉCHARGE DE PRESSION  |   |   |   | 
| CHANGEUR DE PRISES HORS CIRCUIT  |   |   |   | 
| PATTES DE LEVAGE  |   |   |   | 
| ROBINETS DE REMPLISSAGE ET DE VIDANGE D'HUILE  |   |   |   |